Dry-type Transformer

With the development of modern cities, power distribution room especially in high-rise buildings and high fire rating buildings has put forward the requirements of fire prevention and explosion protection according to the relevant fire safety regulations. Dry type transformers then was widely used in high-rise buildings, underground facilities, densely populated areas and humid environments due to its own advantages, such as fire prevention, explosion protection, no pollution, maintenance-free. Therefore , the proportion of dry change is getting higher and higher in the urban power distribution system recent years.

Product Display

With the development of modern cities, electrical rooms—particularly those in high-rise buildings and structures requiring high fire safety ratings—must comply with stringent fire and explosion prevention regulations under fire safety codes. Dry-type transformers, owing to their inherent advantages such as fire resistanceexplosion-proof designpollution-free operation, and maintenance-free performance, have been widely adopted in:

  • High-rise buildings
  • Underground facilities
  • Densely populated areas
  • Humid environments

Consequently, the proportion of dry-type transformers in urban distribution systems has significantly increased in recent years.


Compliance with National Standards

This product series adheres to the following Chinese national standards:

  1. GB 1094Power Transformers
  2. GB/T 10228Technical Parameters and Requirements for Dry-type Power Transformers
  3. GB 20052Energy Efficiency Limits and Grades for Power Transformers

Energy Efficiency Classification

The current product series is categorized into three energy efficiency levels:

  1. SCB18 Class I Efficiency (NX1): Ultra-high efficiency (aligned with IEC 60076-20 Tier 3).
  2. SCB14 Class II Efficiency (NX2): Advanced efficiency (compatible with NEMA TP-1 requirements).
  3. SCB12 Class III Efficiency (NX3): Standard efficiency (meeting baseline market demands).

 

Structural Features

Technical Features of Dry-type Transformers

  1. HV/LV Cast Resin Coils:
    • Robust short-circuit resistanceminimal maintenancehigh operational efficiencycompact footprint, and low noise levels.
    • Ideal for applications demanding fire and explosion prevention, such as commercial complexes and underground substations.
  2. Advanced Casting Process:
    • Employs static mixingvacuum casting, and positive-pressure techniques, ensuring superior mechanical and electrical performance compared to conventional vacuum casting without positive pressure.
  3. Simulation-Optimized Design:
    • Core resonance analysis: Mitigates core cavity resonance to reduce noise (≤55 dB(A) per IEC 60076-10).
    • Lightning impulse simulation: Enhances lightning withstand capability (up to 170kV per IEC 60076-3).
    • Reduced partial discharge: Achieved by optimizing interlayer and segmental electric field distribution (PDIV ≥ 15kV).
  4. Thermal Performance:
    • Thin-layer resin encapsulation prevents cracking and ensures efficient heat dissipation (temperature rise ≤ 80K under rated load).
  5. Overload Capacity:
    • Class H insulation materials for HV/LV windings enable:
      • 110% continuous load in self-cooling mode.
      • 150% continuous load in forced air-cooling mode (per IEEE C57.96).
  6. Intelligent Monitoring System:
    • Integrated temperature protection:
      • Real-time detection and display of three-phase winding temperatures.
      • Auto-start/stop cooling fans with alarm and trip functions (thresholds configurable via IEC 61850 protocols).
  7. Design Advantages:
    • Aesthetic enclosure: Modern industrial design.
    • Space-saving: Compact dimensions reduce floor space requirements.
    • Cost-effective installation: Simplified deployment with minimal civil engineering.

 

Product Specification


10kV dry type  three-phase double-winding unexcited voltage regulation distribution transformer energy efficiency class

Rating capacity

NX1

NX2

NX3

impedance
Silicon steelSilicon steelSilicon steel
No load lossW   load lossNo load lossload lossNo load lossload loss
B
(100℃)
F
(120℃)
H
(145℃)
B
(100℃)
F
(120℃)
H
(145℃)
B
(100℃)
F
(120℃)
H
(145℃)
301056056406851306056406861506707107604
5015584590096518584590096521594010001070
80210116012401330250116012401330295129013801480
100230133014151520270133014151520320148015701690
1252701565166517803201565516651780375174018501980
160310180019152050365180019152050430200021302280
200360213522752440420213522752440495237025302710
250415233024852665490233024852665575259027602960
315510294531253355600294531253355705327034703730
400570337535903850665337535903850785375039904280
500670413043904705790413043904705930459048805230
6307754975529056609104975529056601070553058806290
63075050505365576088550505365576010405610596064006
80087558956265671510355895626567151215655069607460
1000102068857315788512056885731578851415765081308760
12501205819087209335142081908720933516709100969010370
16001415994510555113201665994510555113201960110501173012580
2000176012240130051400520751224013005140052440136001445015560
2500208014535154451660524501453515445166052880161501717018450